Applied Mechanics and Materials, Trans Tech Publications, Ltd., Vol. 602-605 ( 2014-8), p. 2970-2973
Abstract:
In order to solve the problem of low voltage at a terminal rural power grid 66kV substation, a 5000-kilovar SVG is arranged in the substation to elevate and stabilize the 10kV bus voltage. Since put into operation, SVG runs well, solving the problem of low voltage while lowering the loss of the entire line. However, in some cases, people find that while stabilizing the bus voltage, SVG causes voltage drop in adjacent substation, and act of the intelligent capacitor unit in the adjacent substation, thus leading to opposite reactive response of SVG, affecting voltage stabilization of the two substations and adding up to equipment loss. This paper analyzes this phenomenon and has proposed an approach of correction.