In:
MATEC Web of Conferences, EDP Sciences, Vol. 225 ( 2018), p. 02011-
Abstract:
Numerous air conditioners are running without a proper refrigerant charge due to leakage and improper charging during installation. Therefore, there is a need to understand the performance of the air conditioner if it is not properly charged for the means of optimal operation and cost saving. This study is focusing on the usage of a used small capacity split-unit type air conditioner using R-22 refrigerant. The objective is to study the condenser performance over a variation of refrigerant charges. From the results, it is clear that the optimum refrigerant charge is 100%. The highest cooling capacity and COP were 3,330 J/s and 3.05 respectively.
Type of Medium:
Online Resource
ISSN:
2261-236X
DOI:
10.1051/matecconf/201822502011
Language:
English
Publisher:
EDP Sciences
Publication Date:
2018
detail.hit.zdb_id:
2673602-0