In:
IOP Conference Series: Earth and Environmental Science, IOP Publishing, Vol. 647, No. 1 ( 2021-01-01), p. 012013-
Abstract:
After Xiamen VSC-HVDC Project is put into operation, it can improve the power supply capacity and reliability of Xiamen Power Grid.But at the same time,it also brings new problems to the operation of the power grid, among which the short-circuit current problem is particularly prominent.In the preliminary analysis of power grid operation, using the short- circuit current program (PSD-SCCP) commonly used in domestic power grid simulation analysis to calculate to be found that:VSC-HVDC will provide a large short-circuit current when the AC grid is short-circuited, causing the short-circuit current levels of multiple 220kV busbars of the Xiamen Power Grid to approach or exceed 50kA, which brings greater pressure on the adjustment and arrangement of the grid operation mode.Therefore, it is necessary to study the true level of the impact of Xiamen VSC-HVDC on the short-circuit current of the AC grid based on the actual control logic of the Xiamen VSC-HVDC project, in order to propose more accurate short-circuit current suppression measures to achieve bipolar operation of Xiamen VSC-HVDC.
Type of Medium:
Online Resource
ISSN:
1755-1307
,
1755-1315
DOI:
10.1088/1755-1315/647/1/012013
Language:
Unknown
Publisher:
IOP Publishing
Publication Date:
2021
detail.hit.zdb_id:
2434538-6